A.6 drive derating data, Temperature derating, Refer to output current derating due to – Yaskawa J1000 Compact V/f Control Drive User Manual
Page 211: If derating is required. contact a yaskawa sales, Output current derating due to ambient temperature

A.6
Drive Derating Data
The drive can be operated at above rated temperature, altitude and default carrier frequency
by derating the drive capacity.
u
Temperature Derating
As the ambient temperature for the drive is increased above the drive specification the drive
should be derated. Additionally parameter L8-35 Installation Method Selection on page
should be set according to enclosure type and mounting method as illustrated in
.
n
Output Current Derating Due to Ambient Temperature
Set L8-12 and L8-35 according to the installation conditions when the ambient temperature
is above the drive specification or if drives are side-by-side mounted in a cabinet. The output
current is derated as shown in
No.
Name
Description
Range
Def.
L8-12
Ambient
Temperature
Setting
Adjust the drive overload (oL2) protection level when the
drive is installed in an environment that exceeds its ambient
temperature rating.
-10 to 50
30 °C
L8-35
Installation
Method
Selection
0: IP20/IP00 Drive
1: Side-by-Side Mounting
2: NEMA Type 1 Drive
<1>
3: Finless Drive or External Heatsink Installation
0 to 3
0
<1>
This selection assumes that the drive is fitted with the NEMA Type 1 Kit option.
40
50
0
30
o
35
50%
70%
80%
85%
100%
o
o
o
Drive
Rating
Ambient tem
p C
Parameter L8-12
Parameter L8-35 = 0 (IP20/IP00 Drive)
Parameter L8-35 = 2
(NEMA Type 1 Drive)
Parameter L8-35 = 1
(Side-by-side Mounting)
Parameter L8-35 = 3
(Finless Drive or External
Heatsink Installation)
Figure A.1 Ambient Temperature and Installation Method Derating
A.6 Drive Derating Data
YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide
211
A
Specifications