B.3 defaults by drive model and duty rating nd/hd – Yaskawa J1000 Compact V/f Control Drive User Manual
Page 240

Table B.4 Three-Phase 400 V Class Drives Default Settings by Drive Capacity and ND/HD Setting
No.
Description
Unit
Default Settings
−
Model
−
4A0001
4A0002
4A0004
4A0005
o2-04
Drive Model Selection Hex
91
92
93
94
C6-01
Normal/Heavy Duty
−
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
−
Motor rated power
kW
0.37
0.37
0.55
0.75
1.1
1.5
1.5
2.2
C6-02
Carrier frequency
−
3
7
3
7
3
7
3
7
E2-01
Motor rated current
A
0.60
1.00
1.00
1.60
1.60
3.10
3.10
4.20
E2-02
Motor rated slip
Hz
2.50
2.90
2.90
2.60
2.60
2.50
2.50
3.00
E2-03
Motor no-load current
A
0.40
0.60
0.60
0.80
0.80
1.40
1.40
1.50
E2-05
Motor line-to-line
resistance
Ω
83.94
38.20 38.198 22.459 22.459
10.1
10.1
6.495
−
Momentary power loss
ride-through time
s
0.1
0.1
0.1
0.1
0.2
0.2
0.3
0.3
−
Momentary power loss
Baseblock time
s
0.2
0.2
0.2
0.3
0.3
0.4
0.4
0.5
No.
Description
Unit
Default Setting
−
Model
−
4A0007
4A0009
4A0011
o2-04
Drive Model Selection
−
95
96
97
C6-01
Normal/Heavy Duty
−
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
−
Motor rated power
kW
2.2
3.0
3.0
4.0
4.0
5.5
C6-02
Carrier frequency
−
3
7
3
7
3
7
E2-01
Motor rated current
A
4.20
5.70
5.70
7.00
7.00
9.80
E2-02
Motor rated slip
Hz
3.00
2.70
2.70
2.70
2.70
1.50
E2-03
Motor no-load current
A
1.50
1.90
1.90
2.30
2.30
2.60
E2-05
Motor line-to-line resistance
Ω
6.495
4.360
4.360
3.333
3.333
1.595
−
Momentary power loss ride-
through time
s
0.5
0.5
0.5
0.5
0.5
0.5
−
Momentary power loss
Baseblock time
s
0.5
0.5
0.5
0.6
0.6
0.7
B.3 Defaults by Drive Model and Duty Rating ND/HD
240
YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide