B.2 parameter table – Yaskawa J1000 Compact V/f Control Drive User Manual
Page 232

No.
Name
Description
Range Def. Mode Addr.
Hex
Pg.
L8-05
Input Phase
Loss
Protection
Selection
Selects the detection of input current phase loss,
power supply voltage imbalance, or main circuit
electrolytic capacitor deterioration.
0: Disabled
1: Enabled
Note: This parameter is disabled in 200 V single-
phase drives.
0, 1
1
O
4B1
–
L8-10
Heatsink
Cooling Fan
Operation
Selection
Controls the heatsink cooling fan operation.
0: Run with timer (Fan operates only during run and
for 60 seconds after stop.)
1: Run always (Cooling fan operates whenever the
drive is powered up.)
0, 1
0
O
4B6
–
L8-12 Ambient
Temperature
Setting
Used to input the ambient temperature. This value
adjusts the drive oL2 detection level.
-10 to
50
30 °C
O
4B8
–
L8-18 Soft Current
Limit
Selection
Selects the software current limit function. Typically
no adjustment is required.
0: Disabled
1: Enabled
0, 1
1
O
4BE
–
L8-35
<3>
Installation
Method
Selection
Selects the installation type:
0: IP20/IP00 Drive
1: Side-by-Side Mounting
2: NEMA Type 1 Drive
3: Finless Drive or External Heatsink Installation
0 to 3
0
O
4EC
–
L8-38 Carrier
Frequency
Reduction
Provides protection to the IGBTs by reducing the
carrier frequency at low speeds.
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the whole speed range
Current
C6-02
Carrier Frequency
ND
HD
2
0
200 V Single Phase
80% of HD
10 (8)
15
400 V: 60% of HD
0 to 2
1
O
4EF
–
<1>
When enabled, the drive stops accelerating when it exceeds the value of L3-02, Stall Prevention Level. The drive
decelerates after 100 ms and begins accelerating again after restoring the current level.
<2>
Default setting value is 120% when C6-01 is set to 1 (ND) and 150% when C6-01 is set to 0 (HD).
<3>
This parameter is not reset to the default value when the drive is reinitialized using A1-03.
<4>
The default setting and the upper limit of the setting range are determined by C6-01, Drive Duty Mode, and
L8-38, Carrier Frequency Reduction Selection.
B.2 Parameter Table
232
YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide