• Disable motor protection (L1-01 = 1) when running multiple motors from the same drive.
Attach a thermal relay for each motor to provide overload protection.
• Use L1-13 (Continuous Electrothermal Operation Selection) to select whether the
electrothermal value is “held” or “not held” when power supply is turned off. Default setting
is 1 (Enabled).
• In the case of a general purpose (standard) motor, the cooling capability is reduced at a low
speed. Motor overload protection (oL1) may occur in frequencies lower than motor rated
current. Use an exclusive-use or inverter-duty motor to operate the drive at rated current at
low frequency.
u
Drive Status Monitors: U1-01 to U4-13
Parameter group U displays various data regarding the operating status of the drive.
The following example demonstrates viewing output voltage reference (U1-06).
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
2.
Press
until “Monitor Display” appears.
3.
Press
to enter the Parameter Setting Screen.
4.
Press
until U1-06 appears.
5.
Press
to display the voltage reference. The Output Voltage
Reference appears.
Refer to Parameter List on page 213
for more details about Drive Status Monitors.
Table 4.13 Drive Status Monitors
No.
Parameter Name
Page
U1-01 Frequency Reference
U1-02 Output Frequency
U1-03 Output Current
U1-06 Output Voltage Reference
U1-07 DC Bus Voltage
U1-10 Input Terminal Status
U1-11 Output Terminal Status
U1-13 Terminal A1 Input Voltage
No.
Parameter Name
Page
U1-19 MEMOBUS/Modbus Error Code
U1-25 Software Number (ROM)
U1-26 Software Number (Flash)
U2-01 Current Fault
U2-02 Previous Fault
U4-01 Accumulated Operation Time
U4-04 Cooling Fan Maintenance
U4-05 Capacitor Maintenance
4.5 Basic Operation
110
YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide