A.5 drive watt loss data – Yaskawa J1000 Compact V/f Control Drive User Manual
Page 209

A.5
Drive Watt Loss Data
Table A.4 Watt Loss 200 V Class Single-Phase Models
Drive
Model
Heavy Duty (Carrier Frequency 8/10 kHz)
<1>
Normal Duty (Swing PWM equal 2 kHz)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
BA0001
0.8
4.3
7.4
11.7
1.2
5.0
8.5
13.5
BA0002
1.6
7.9
8.9
16.7
1.9
7.6
9.7
17.3
BA0003
3.0
16.1
11.5
27.7
3.3
14.6
14.4
29.1
BA0006
5.0
33.7
16.8
50.5
6.0
30.1
19.4
49.5
BA0010
8.0
54.8
25.9
80.7
9.6
51.7
29.8
81.4
<1>
10 kHz for BA0001 to BA0006
Table A.5 Watt Loss 200 V Class Three-Phase Models
Drive
Model
Heavy Duty (Carrier Frequency 8/10 kHz)
<1>
Normal Duty (Swing PWM equal 2 kHz)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
2A0001
0.8
4.3
7.3
11.6
1.2
5.0
8.0
13.0
2A0002
1.6
7.9
8.8
16.7
1.9
7.6
9.5
17.1
2A0004
3.0
16.2
11.5
27.7
3.5
15.8
13.6
29.4
2A0006
5.0
27.4
15.9
43.3
6.0
27.5
17.2
44.7
2A0010
8.0
54.8
23.8
78.6
9.6
51.7
25.8
77.5
2A0012
11.0
70.7
29.9
100.6
12.0
61.3
30.4
91.7
2A0020
17.5
110.5
43.3
153.8
19.6
98.7
46.3
145.0
<1>
10 kHz for 2A0001 to2A0006
Table A.6 Watt Loss 400 V Class Three-Phase Models
Drive
Model
Heavy Duty (Carrier Frequency 8 kHz)
Normal Duty (Swing PWM equal 2 kHz)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
4A0001
1.2
19.2
11.5
30.7
1.2
10.0
9.6
19.6
4A0002
1.8
28.9
14.8
43.7
2.1
18.5
13.9
32.4
4A0004
3.4
42.3
17.9
60.2
4.1
30.5
16.8
47.3
4A0005
4.8
70.7
26.2
96.9
5.4
44.5
21.8
66.3
A.5 Drive Watt Loss Data
YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide
209
A
Specifications