Yaskawa F7 to L1000A User Manual
Page 9
(Header Title) Application Note
Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.
©2010 www.yaskawa.com September 9, 2010 9 of 57
Subject: Transition Guide
Product: L1000A
Document: PL.L1000A.01
Title: Product Transition Guide – F7 to L1000A
Product Transition Guide – F7 to L1000A
Control Circuit
Terminal
Signal Level
F7
L1000A
Name
F7
L1000A
SN
Digital Input Supply Common
0V
RP
Multi-function pulse train input
Response frequency
0 to 32 kHz (3 kΩ)
―
+V
+15 V
(20 mA max)
+10.5 V
*
(20 mA max)
-
V
For frequency reference input
* L1000A has a lower voltage level for this terminal. The setting
range for the frequency reference needs to be adjusted.
-15 V
(20 mA max)
-10.5 V
*
(20 mA max)
A1
Main speed reference
(multi-function analog input terminal in L1000A)
0 to +10 Vdc (20 kΩ)
0±10 V
0 to +10 Vdc (20 kΩ)
0±10 V
A2
Multi-function analog input
0 to +10 Vdc (20 kΩ)
0±10 V
4 to 20 mA (250Ω)
0 to +10 Vdc (20 kΩ)
0±10 V
4 to 20 mA (250Ω)
0 to 20 mA (250Ω)
A3
Multi-function analog input
0±10 Vdc (20 kΩ)
―
AC
Analog common
(frequency reference circuit common in L1000A)
0 V
HC*
Safe Disable input common
24 Vdc, 8 mA max
H1*
H2*
Safe Disable input
Open: Motor coasts
Closed: Normally operation
*Make sure a wire jumper is
between terminals HC-H1
and HC-H2
DM+
_
DM-
Safe Disable monitor output
―
Signal Level
+48 Vdc, 50 mA max
MA
Fault output (N.O.)
MB
Fault output (N.C.)
MC
Contact output common
M1
M2
Multi-function relay output 1
F7 (During run)
L1000A (Brake Release Command)
M3
M4
Multi-function relay output 2
F7 (Zero Speed)
L1000A (Output Contactor Close Command)
M5
M6
Multi-function relay output 2
F7 (Frequency Agree)
L1000A (Drive Ready)
Contact output
30 Vdc 10 mA to 1 A
250 Vac 10 mA to 1 A
Minimum Load: 5Vdc, 10mA