Terminal connections – Yaskawa F7 to L1000A User Manual
Page 7
(Header Title) Application Note
Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.
©2010 www.yaskawa.com September 9, 2010 7 of 57
Subject: Transition Guide
Product: L1000A
Document: PL.L1000A.01
Title: Product Transition Guide – F7 to L1000A
Product Transition Guide – F7 to L1000A
F7
L1000A
Power
Supply
Model
CIMR-F7U
□
Rated
Output
Capacity
(HP)
Rated
Output
Current
(A)
Carrier
Frequency
(kHz)
Model
CIMR-LU
□
Rated
Output
Capacity
(HP)
Rated
Output
Current
(A)
Carrier
Frequency
(kHz)
43P7 5 6.9
4A0009
5 9.2
45P5 7.5 11.4
4A0015 7.5 14.8
47P5 10 15.5
4A0018 10 18
4011 15 21.9
4A0024
15 24
4015 20 28.3
4A0031
20 31
4018 25 35.6
4A0039
25 39
4022
30 41
4A0045
30 45
4030 40 50.5
4A0060
40 60
4037 50 63.2
4A0075
50 75
4045 60 76.6
4A0091
60 91
4055 75 94.3
4A0112
75 92
4075 100 110.4
4A0150
100 123
4090 125 132.5
4A0180
125 148
4110 150 159
4A0216
150 177
400 V
3-Phase
4132 200 194.4
8
4A0260 200 213
8
Terminal Connections
Main Circuit Terminals
Note:
The F7 and L1000A drives may have different terminal sizes (depending on capacity). The terminals must be carefully
checked before replacement.
Main Circuit Terminal
F7
L1000A
Comments
R/L1 R/L1
S/L2 S/L2
T/L3 T/L3
Main circuit power supply input
R1/L11
―
S1/L21
―
T1/L31
―
Main circuit power supply input
U/T1 U/T1
V/T2 V/T2
W/T3 W/T3
Drive output
B1 B1
B2 B2
Terminal connections for braking resistor or braking resistor units
+1 +1
DC reactor, DC power supply input (positive)
+2 +2
DC reactor
+3 +3
Braking unit connection (positive)
―
―
Negative terminals (for DC power supply and braking units)
r/
1
―
Cooling fan power supply
C t l
l