(Header Title) Application Note




Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.

©2010 www.yaskawa.com September 9, 2010 49 of 57

Subject: Transition Guide

Product: L1000A

Document: PL.L1000A.01

Title: Product Transition Guide – F7 to L1000A

Product Transition Guide – F7 to L1000A

F7

L1000A

Parameter Name

Parameter

Default

Setting

Record

Parameter

Default

Comments:

Gray shading indicates default setting.

Operation when Frequency
Reference is Missing

L4-05 0 L4-05 0

F7 L1000A

L4-05 L4-05
0: Stop

0: Stop

1: Continue operating at
80% speed

1: Continue operating at the
level set to L4-06

Speed Reference at
Reference Loss

L4-06

80 %

L4-06

80 %

Door Zone Level

L4-13*

0.0 %

Sets the door zone speed level.

Number of Auto Restart
Attempts

L5-01

0 times

L5-01

0 times

Auto Restart Operation
Selection

L5-02 0 L5-02 0

F7 L1000A

L5-02 L5-02
0: No output

0: No output

1: Outputs during restart

1: Outputs during restart

Fault Reset Interval Time

L5-04

10.0

s

F

ault Re

sta

rt

UV1 Fault Reset Selection

L5-06* 0

0: Same as the L5-01 selection.
1: Always automatically reset UV1.

Torque Detection Selection 1

L6-01

0

L6-01

0

F7 L1000A

L6-01, L6-04

L6-01, L6-04

0: Disabled

0: Disabled

1: oL3 detection only active
during speed agree,
operation continues after
detection

1: oL3 detection only active
during speed agree,
operation continues after
detection

2: oL3 detection always
active during run, operation
continues after detection

2: oL3 detection always
active during run, operation
continues after detection

3: oL3 detection only active
during speed agree, output
shuts down on an oL3 fault

3: oL3 detection only active
during speed agree, output
shuts down on an oL3 fault

4: oL3 detection always
active during run, output
shuts down on an oL3 fault

4: oL3 detection always
active during run, output
shuts down on an oL3 fault

5: UL3 detection only active
during speed agree,
operation continues after
detection

5: UL3 detection only active
during speed agree,
operation continues after
detection

6: UL3 detection always
active during run, operation
continues after detection

6: UL3 detection always
active during run, operation
continues after detection

7: UL3 detection only active
during speed agree, output
shuts down on an oL3 fault

7: UL3 detection only active
during speed agree, output
shuts down on an oL3 fault

8: UL3 detection always
active during run, output
shuts down on an oL3 fault

8: UL3 detection always
active during run, output
shuts down on an oL3 fault

Torque Detection Level 1

L6-02

150%

L6-02

150%

Torque Detection Time 1

L6-03

0.1 s

L6-03

0.1 s

Torque Detection Selection 2

L6-04

0

*

L6-04 0

*

*See the L6-01 description for OL4 and UL4.

Torque Detection Level 2

L6-05

150%

L6-05

150%

Over

torque

Detecti

on

Torque Detection Time 2

L6-06

0.1 s

L6-06

0.1 s

Forward Torque Limit

L7-01

200%

L7-01

200%

Reverse Torque Limit

L7-02

200%

L7-02

200%

Torque Limi

t

Forward Regenerative Torque
Limit

L7-03 200% L7-03 200%