Ratings summary – Yaskawa F7 to L1000A User Manual
Page 6
(Header Title) Application Note
Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.
©2010 www.yaskawa.com September 9, 2010 6 of 57
Subject: Transition Guide
Product: L1000A
Document: PL.L1000A.01
Title: Product Transition Guide – F7 to L1000A
Product Transition Guide – F7 to L1000A
Classification
Item
Checklist
Check
Braking Resistor
Check to see if the F7 drive currently used has a braking resistor installed.
For F7 drives 3.7 kW and smaller using an ERF-type braking resistor, check the
following:
•
Verify the braking specifications match the equivalent L1000A replacement unit.
See the Braking Resistor Installation Attachment section of this guide for
specifications. Use only the braking resistor recommended by Yaskawa.
•
If planning to use the same ERF-type braking resistor installed to F7 in the new
L1000A drive and the cable is too short, replace the cable with a longer one only
if the wire specifications are the same.
Braking units
If braking unit is used, it can simply be transferred over to L1000A as-is.
For braking units 30 kW and below, braking transistor protection should be disabled
in L1000A (L8-55 = 0).
AC or DC Reactor
See if the F7 has an AC or DC reactor that can be reused with L1000A
Option &
Other
Peripherals
Noise Filter
If a noise filter is used, it can simply be used with L1000A as-is.
•
Thoroughly review the instruction manual included with the new drive.
•
To request a catalog, product manual, pricing, or shipping dates, please call your local Yaskawa sales office
or representative.
•
For technical questions, support, or other related information, contact a Yaskawa representative.
Ratings Summary
F7
L1000A
Power
Supply
Model
CIMR-F7U
□
Rated
Output
Capacity
(HP)
Rated
Output
Current
(A)
Carrier
Frequency
(kHz)
Model
CIMR-LU
□
Rated
Output
Capacity
(HP)
Rated
Output
Current
(A)
Carrier
Frequency
(kHz)
23P7 5 13.9
2A0018
5 17.5
25P5
7.5 21
2A0025
7.5 25
27P5
10 28
2A0033
10 33
2011
15 41
2A0047
15 47
2015 20 52.9
2A0060
20 60
2018 25 64.8
2A0075
25 75
2022 30 77.5
2A0085
30 85
2030 40 96.8
2A0115
40 115
2037 50 107
2A0145
50 128
2045 60 132.5
2A0180
60 158
2055 75 158.2
2A0215
75 189
2075 100 208.3
2A0283
100 249
2090 125 254.7
8
2A0346 125 304
200 V
3-Phase
2110 150 360
2
2
2A0415 150 365
8