(Header Title) Application Note




Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.

©2010 www.yaskawa.com September 9, 2010 50 of 57

Subject: Transition Guide

Product: L1000A

Document: PL.L1000A.01

Title: Product Transition Guide – F7 to L1000A

Product Transition Guide – F7 to L1000A

F7

L1000A

Parameter Name

Parameter

Default

Setting

Record

Parameter

Default

Comments:

Gray shading indicates default setting.

Reverse Regenerative Torque
Limit

L7-04 200% L7-04 200%

Internal Dynamic Braking
Resistor Protection Selection
(ERF)

L8-01 0 ─

No corresponding parameter in L1000A.

Overheat Pre-Alarm Level

L8-02

*

L8-02

*

Determined by drive capacity.

Overheat Pre-Alarm
Operation Selection

L8-03 3 L8-03 3

F7 L1000A

L8-03 L8-03
0: Ramp to stop

0: Ramp to stop

1: Coast to stop

1: Coast to stop

2: Fast Stop

2: Fast Stop

3: Continue operation

3: Continue operation

Input Phase Loss Protection
Selection

L8-05 0 L8-05 1

F7 L1000A

L8-05 L8-05
0: Disabled

0: Disabled

1: Enabled

1: Enabled

Input Phase Loss Detection
Level

L8-06

*

Determined by drive capacity.

Output Open-Phase
Protection Selection

L8-07 0 L8-07 0

F7 L1000A

L8-07 L8-07
0: Disabled

0: Disabled

1: Enabled (triggered by a
single phase loss)

1: Enabled (triggered by a
single phase loss)

2: Enabled (triggered when
two phases are lost)

2: Enabled (triggered when
two phases are lost)

H

ar

dw

ar

e P

rot

ec

tion

Ground Protection Selection

L8-09

1

L8-09

1

F7 L1000A

L8-09 L8-09
0: Disabled

0: Disabled

1: Enabled

1: Enabled

Cooling Fan Control Selection

L8-10

0

L8-10

0

F7 L1000A

L8-10 L8-10
0: During run only

0: During run only

1: Fan always on

1: Fan always on

2: Temp Controlled
Operation

Cooling Fan Control Delay
Time

L8-11

60 s

L8-11

60 s

Ambient Temperature Setting

L8-12

45℃

L8-12

40℃

Set the ambient temperature where the drive is being used.

oL2 Characteristics Selection
at Low Speeds

L8-15 1 L8-15 1

F7 L1000A

L8-15 L8-15
0: Disabled

0: Disabled

1: Enabled

1: Enabled

Soft CLA Selection

L8-18

1

No corresponding parameter in L1000A.

Current Unbalance Detection

L8-29 1

L1000A

L8-29

0: Disabled

1: Enabled

Internal Cooling Fan Failure
OH1 Detection

L8-32 1 ─

F7 L1000A

L8-32

0: Alarm detection

1: Fault detection

L1000A does not have an
internal cooling fan