(Header Title) Application Note




Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.

©2010 www.yaskawa.com September 9, 2010 8 of 57

Subject: Transition Guide

Product: L1000A

Document: PL.L1000A.01

Title: Product Transition Guide – F7 to L1000A

Product Transition Guide – F7 to L1000A

Main Circuit Terminal

F7

L1000A

Comments

/

2

200/

2

200

400/

2

400

Grounding: 200 V class: Ground to 100

Ω or less

400 V class: Ground to 10

Ω or less


Control Terminals and Signal Levels

Terminal function differences between F7 and L1000A are listed in the table below.

The table indicates terminals in F7 that do not exist in L1000A.

Terminals H1 and H2 in the L1000A are for the Safe Disable feature.
Do not remove the jumper between H1-HC and H2-HC.

Control Circuit

Terminal

Signal Level

F7

L1000A

Name

F7

L1000A

S1

F7 (Closed: Forward Run, Open: Stop)
L1000A (Closed: Up, Open: Stop)

S2

F7 (Closed: Reverse Rrun, Open: Stop)
L1000A (Closed: Down, Open: Stop)

S3

Multi-Function Input Selection 1
F7 (External fault, N.O.)
L1000A (Nominal Speed)

S4

Multi-Function Input Selection 2
F7 (Fault reset)
L1000A (Inspection Operation)

S5

Multi-Function Input Selection 3
F7 (Multi-Step Speed Reference 1)
L1000A (Intermediate Speed 1)

S6

Multi-Function Input Selection 4
F7 (Multi-Step Speed Reference 2)
L1000A (Leveling Speed)

S7

Multi-Function Input Selection 5
F7 (Jog)
L1000A (Not Used)

S8

Multi-Function Input Selection 6
F7 (External baseblock command)
L1000A (Not Used)



Photocoupler insulation
24 Vdc, 8 mA

Use the wire jumper between SC and SN or between SC
and SP to select sinking or sourcing, and to select the
power supply.



SC


Sequence Control Input Common

Common Control Signal

(2 terminals)

(2 terminals)