Yaskawa F7 to L1000A User Manual
Page 11
(Header Title) Application Note
Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.
©2010 www.yaskawa.com September 9, 2010 11 of 57
Subject: Transition Guide
Product: L1000A
Document: PL.L1000A.01
Title: Product Transition Guide – F7 to L1000A
Product Transition Guide – F7 to L1000A
Terminal Sizes and Wire Gauges
Note: The table below lists the wiring sizes based on JIS electrical codes. Gauges are recommended, and users may
select different gauges at their own discretion. F7 lists gauges meeting UL approval. For UL requirements covering
wire gauges in the United States and wire gauges in Europe, refer to Chapter 3. Electrical Installation in the L1000A
Quick Start Guide (TOEPC71061638).
Main Terminal Size/Electrical Wiring Differences.
Indicates ground terminal
Power
Supply
Model
Model
Terminal Signal
Terminal
Screw
Tightening Torque
lb. In.
(N・M)
Allowable Wire
Range AWG
(mm
2
)
Suggested
Wire Size
AWG (mm
2
)
F7 23P7
R/L1,S/L2,T/L3,
U/T1,V/T2,W/T3,
-
,+1, +2, B1, B2,
M4
10.6 to 13.2 (1.2 to 1.5)
12 to 10
(3.5 to 5.5)
12(3.5)
R/L1,S/L2,T/L3,
M4
18 to 10 (0.75 to 5.5)
10 (5.5)
-
,+1, +2
M4
12 to 10 (3.5 to 5.5)
—
U/T1,V/T2,W/T3,
M4
18 to 10 (0.75 to 5.5)
10 (5.5)
L1000A 2A0018
B1, B2
M4
10.6 to 13.2 (1.2 to 1.5)
14 to 10 (2 to 5.5)
—
F7 25P5
R/L1, S/L2, T/L3,U/T1,
V/T2, W/T3,-, +1, +2,
B1, B2,
M4
10.6 to 13.2 (1.2 to 1.5)
12 to 10 (3.5 to 5.5)
10 (5.5)
R/L1, S/L2, T/L3,
M4
12 to 6 (3.5 to 14)
8 (8)
200 V
Class
-
, +1, +2
M4
10 to 6 (5.5 to 14)
—
U/T1, V/T2, W/T3
M4
12 to 6 (3.5 to 14)
8 (8)
B1, B2
M4
10.6 to 13.2 (1.2 to 1.5)
12 to 10 (2 to 5.5)
—
L1000A 2A0025
M5
17.7 to 22.1 (2 to 2.5)
10 to 8 (5.5 to 8)
8 (8)
F7 27P5
R/L1, S/L2, T/L3,U/T1,
V/T2, W/T3,-, +1, +2,
B1, B2,
M5
21.99 (2.5)
8 to 6 (8 to 14)
8 (8)
R/L1, S/L2, T/L3,
M4
12 to 6 (3.5 to 14)
14 (2)
-
, +1, +2
M4
6 (14)
—
U/T1, V/T2, W/T3
M4
12 to 6 (3.5 to 14)
8 (8)
B1, B2
M4
10.6 to 13.2 (1.2 to 1.5)
12 to 10 (3.5 to 5.5)
—
L1000A 2A0033
M5
17.7 to 22.1 (2 to 2.5)
10 to 8 (5.5 to 8)
8 (8)