(Header Title) Application Note
Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.
©2010 www.yaskawa.com September 9, 2010 41 of 57
Subject: Transition Guide
Product: L1000A
Document: PL.L1000A.01
Title: Product Transition Guide – F7 to L1000A
Product Transition Guide – F7 to L1000A
F7
L1000A
Parameter Name
Parameter
Default
Setting
Record
Parameter
Default
Comments:
Gray shading indicates default setting.
Digi
tal i
nputs Terminal S7 Function
Selection
H1-05
6 (4)
H1-07*
5 (F)
F7 L1000A
25: External fault (N.C.,
Always detected, Coast to
stop)
25: External fault (N.C.,
Always detected, Coast to
stop)
26: External fault (N.O.,
Detected during run, Coast
to stop)
26: External fault (N.O.,
Detected during run, Coast
to stop)
27: External fault (N.C.,
Detected during run, Coast
to stop)
27: External fault (N.C.,
Detected during run, Coast
to stop)
28: External Fault (N.O.,
always detected, Fast Stop)
28: External Fault (N.O.,
always detected, Fast Stop)
29: External fault (N.C.,
always detected, Fast Stop)
29: External fault (N.C.,
always detected, Fast Stop)
2A: External Fault (N.O.,
detected during run, Fast
Stop)
2A: External Fault (N.O.,
detected during run, Fast
Stop)
2B: External fault (N.C.,
detected during run, Fast
Stop)
2B: External fault (N.C.,
detected during run, Fast
Stop)
2C: External fault (N.O.,
always detected, alarm
only)
2C: External fault (N.O.,
always detected, alarm
only)
2D: External fault (N.C.,
always detected, alarm
only)
2D: External fault (N.C.,
always detected, alarm
only)
Digi
tal Inpu
ts
Terminal S8 Function
Selection
H1-06 8
(6) H1-08
F
F7 L1000A
2E: External Fault
(N.O., detected during run,
alarm only)
2E: External Fault (N.O.,
detected during run, alarm
only)
2F: External Fault (N.C.,
detected during run, alarm
only)
2F: External Fault (N.C.,
detected during run, alarm
only)
30: PID control integral
reset
─
31: PID control integral hold
─
32: Multi-step speed
reference 4
─
34: PID Soft Starter switch
─
35: PID input characteristics
switch
─
─
50: Nominal Speed
─
51: Intermediate Speed
─
52: Releveling Speed
─
53: Leveling Speed
─ 54:
Inspection
Operation
─ 55:
Rescue
Operation
─
56: Motor Contactor
Feedback