(Header Title) Application Note




Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.

©2010 www.yaskawa.com September 9, 2010 40 of 57

Subject: Transition Guide

Product: L1000A

Document: PL.L1000A.01

Title: Product Transition Guide – F7 to L1000A

Product Transition Guide – F7 to L1000A

F7

L1000A

Parameter Name

Parameter

Default

Setting

Record

Parameter

Default

Comments:

Gray shading indicates default setting.

Digi

tal Inpu

ts

Terminal S5 Function
Selection

H1-03

3 (0)

H1-05*

3 (51)

Terminal S6 Function

Selection

H1-04

4 (3)

H1-06*

4 (53)

F7 L1000A

H1-01 to H1-06

H1-03 to H1-08

F: Not used

F: Not used

10: Up command

11: Down command

12: FWD jog

13: REV jog

14: Fault Reset

14: Fault Reset

15: Fast Stop (N.O.)

15: Fast Stop (N.O.)

16: Motor switch command 16: Motor switch command
17: Fast Stop (N.C.)

17: Fast Stop (N.C.)

18: Timer function input

18: Timer function input

19: PID control cancel

1A: Accel/decel time
selection 2

1A: Accel/decel time
selection 2

1B: Write allowed

1C: +Speed Command

1D: -Speed Command

1E: Analog freq ref sample /
hold

20: External fault (N.O.,
Always detected, Ramp to
stop)

20: External fault (N.O.,
Always detected, Ramp to
stop)

21: External fault (N.C.,
Always detected, Ramp to
stop)

21: External fault (N.C.,
Always detected, Ramp to
stop)

22: External fault (N.O.,
Detected during run, Ramp
to stop)

22: External fault (N.O.,
Detected during run, Ramp
to stop)

23: External fault (N.C.,
Detected during run, Ramp
to stop)

23: External fault (N.C.,
Detected during run, Ramp
to stop)

24: External fault (N.O.,
Always detected, Coast to
stop)

24: External fault (N.O.,
Always detected, Coast to
stop)