(Header Title) Application Note
Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.
©2010 www.yaskawa.com September 9, 2010 52 of 57
Subject: Transition Guide
Product: L1000A
Document: PL.L1000A.01
Title: Product Transition Guide – F7 to L1000A
Product Transition Guide – F7 to L1000A
F7
L1000A
Parameter Name
Parameter
Default
Setting
Record
Parameter
Default
Comments:
Gray shading indicates default setting.
Feed Forward Control Ratio
Gain
n5-03 1.00 n5-03 1.00
─
Speed Reference Response
Frequency
n5-04 40.00
Hz
─
─
No corresponding parameter in L1000A.
D
is
play Sett
ing
/
Selection
Drive Mode Unit Monitor
Selection
o1-01 6
*
o1-01
106
*
*See the comments given for parameter F4-01.
User Monitor Selection After
Power Up
o1-02 1 o1-02 1
F7 L1000A
o1-02 o1-02
1: Frequency reference
1: Frequency reference
2: Output frequency
2: Direction
3: Output current
3: Output Frequency
4: Determined by o1-01
4: Output Current
─
5: User-selected Monitor
D
is
play Sett
ing
/ Selec
tion
Frequency Units of Reference
Setting and Monitor
o1-03
0
o1-03
1
F7 L1000A
o1-03 o1-03
0: 0.01 Hz units
0: 0.01 Hz units
1: 0.01% units
1: 0.01% units
2 to 39: r/min units
2: r/min units
40 to 39999: User-set units
3: User-set units
o1-10 o1-11
1 to 60000
0 to 3
─
4: Elevator units 1
─
5: Elevator units 2
─
6: Elevator units 3
o1-10: Determines how the units for the frequency
reference.
o1-11: Sets the decimal point for the frequency reference
display.
Ex. : For a max output frequency of 200.0, set the following:
F7 L1000A
Setting value:
o1-03=12000
Setting value:
o1-03=3
o1-10=2000
o1-11=1
1 2 0 0 0
│ └ Max value, excluding decimal point → o1-10= “2000”
└── digits displayed to the right of the decimal →o1-11=
1
Setting Unit for Frequency
Constants Related to V/f
Characteristics
o1-04 0 o1-04 0
F7 L1000A
o1-04 o1-04
0: Hz units
0: Hz units
1: r/min units
1: r/min units
LCD Brightness
o1-05
3
─
─
No corresponding parameter in L1000A.
Length Units
─
─
o1-12 0
0: Millimeter unit
1: Inch Unit