(Header Title) Application Note




Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.

©2010 www.yaskawa.com September 9, 2010 43 of 57

Subject: Transition Guide

Product: L1000A

Document: PL.L1000A.01

Title: Product Transition Guide – F7 to L1000A

Product Transition Guide – F7 to L1000A

F7

L1000A

Parameter Name

Parameter

Default

Setting

Record

Parameter

Default

Comments:

Gray shading indicates default setting.

Terminal M3 and M4 Function

Selection

H2-02 1 H2-02 51

Terminal M5 and M6 Function

Selection

H2-03 2 H2-03 6

Digi

tal Outp

ut

s

Terminal P1 Function
Selection

H2-04 37

F7 L1000A

H2-01 to H2-03

H2-01 to H2-05

19: Torque detection 2
(N.C.)

1A: Reverse run

1A: During Down Direction

1B: During baseblock 2
(N.C.)

F: Not Used

1C: Motor selection

1D: Regen during run

1E: Fault restart

1E: Fault restart

1F: Motor overload alarm

1F: Motor overload alarm

20: Drive overheat alarm

20: Drive overheat alarm

2F: Maintenance timer

30: During torque limit

30: During torque limit

31: During speed limit

32: Speed limit active

33: Zero servo complete

33: Within Position Lock

36: Frequency detection 5

37: During run 2

37: During frequency output

50: Brake Control

51: Output Contactor
Control

52: Door Zone Reached

53: Not Zero Speed

54: Light Load Direction

55: Light Load Direction
Detection Status

56: Cooling Fan Status

57: Input Phase Loss

58: Safe Disable Status

3D: Cooling fan malfunction

61: Rotor detection
complete

100-161: 0 to 61 with
Inverse Output