beautypg.com

14 technical data, 1 windy boy 3600tl, Technical data – SMA WB 3600TL User Manual

Page 85: Windy boy 3600tl

background image

SMA Solar Technology AG

Technical Data

Installation Guide

WB36TL_50TL-IEN102011

85

14 Technical Data

14.1 Windy Boy 3600TL

DC Input

AC Output

* Depends on country configuration

Maximum DC voltage

550 V

MPP input voltage range

80 V … 440 V

Maximum open circuit voltage to activate "Turbine Mode"

125 V

DC nominal voltage

400 V

Maximum input current

2 x 15 A

Maximum DC power

3,800 W

Voltage ripple

< 10 % of the input voltage

Nominal AC power

3,600 W

Maximum AC power

3,600 W

Nominal AC current

15.7 A

Maximum output current

22 A

Maximum fuse protection

32 A

Harmonic distortion of output current at
AC THD voltage < 2 %,
AC power > 0.5 AC nominal power

< 3 %

Nominal AC voltage

220 V / 230 V / 240 V

AC voltage range, extended operating range*

180 V … 280 V

AC grid frequency*

50 Hz / 60 Hz

Tolerance at AC grid frequency

± 5 Hz

Power factor at nominal AC power

1

Overvoltage category

III

Test voltage at 50 Hz
(1 s routine testing / 5 s type testing)

1.4 kV

Surge testing voltage

4 kV

Serial interface

6 kV

Internal consumption in standby

< 0.5 W

This manual is related to the following products: