8 Restarting the system
1. Check the DC plug connector for correct polarity.
2. Connect one positive and one negative DC plug
connector each to both input areas on the inverter.
To release the DC plug connectors see
section 7.2 ”Disconnect the device from voltage
sources” (page 59).
Never connect all four DC plug connectors to only
one input area!
3. To create the seal on the inverter, all DC inputs that
are not required must be closed as follows:
– Insert the sealing plugs provided into the DC
plug connectors that are not needed. Do not
insert the sealing plugs into the DC inputs on the
inverter.
– Insert the DC plug connectors with sealing plugs
into the corresponding DC inputs on the inverter.