7 disconnecting the inverter, 1 safety, 2 disconnect the device from voltage sources – SMA WB 3600TL User Manual
Page 59: Disconnecting the inverter, Safety, Disconnect the device from voltage sources

SMA Solar Technology AG
Disconnecting the Inverter
Installation Guide
WB36TL_50TL-IEN102011
59
7 Disconnecting the Inverter
7.1 Safety
7.2 Disconnect the device from voltage sources
1. Stop the small wind turbine system and secure against restart.
2. Disconnect the line circuit breaker and secure against re-connection.
3. Disconnect the multi-function relay, if available.
4. Remove the Electronic Solar Switch.
5. Wait until LEDs, display and if applicable the fault indicator have gone off.
DANGER!
Danger to life due to high voltages in the inverter.
The inverter operates at high voltages.
• Disconnect the inverter as described in the following section.
DANGER!
Danger to life due to high voltages in the inverter.
The capacitors in the inverter require 5 minutes to discharge.
• Wait 5 minutes before opening the inverter.