Messages

SMA Solar Technology AG

76

WB36TL_50TL-IEN102011

Installation Guide

73

< Update main CPU failed >
Internal device fault.

• Contact the SMA Serviceline (see

section 16 ”Contact” (page 92)).

< Update RS485I module failed >
Internal device fault: however, the inverter
continues to feed in.

• Retry update.
• If this fault occurs again, contact the

SMA Serviceline (see
section 16 ”Contact” (page 92)).

< Update BT failed >
Internal device fault: however, the inverter
continues to feed in.
< Upd. display failed >
Internal device fault: however, the inverter
continues to feed in.
< Update language table failed >
Internal device fault: however, the inverter
continues to feed in.

74

< Varistor defective >

• Check the varistors as described in

section 12.2 ”Checking the
Functioning of the Varistors”
(page 80).

80

< Derating occurred >
The delivered power of the inverter was
reduced below nominal power due to a
too-high temperature for more than
10 minutes.

If this event occurs often:

• Ensure sufficient ventilation.
• Check heat dissipation, as described

in section 9.1 ”Checking Heat
Dissipation” (page 65).

90

< Inst. Code invalid >
The entered installer code (personal) is
invalid.

• Enter valid Grid Guard Code.

< Grid param. locked >
The actual country data set is locked.

• Enter valid Grid Guard Code to

change the country data set.

< Waiting for main CPU >

• DC voltage at the DC input is not

sufficient to run the main computer.

• The selected rotary switch setting for

the country configuration is not
programmed.

• The parameters to be changed are

protected.

• Ensure sufficient DC voltage (green

LED lights up or flashes).

• Check the setting of the rotary

switches (see section 5.4.2).

• Enter Grid Guard Code.

Event no. Cause

Corrective measures