SMA Solar Technology AG

Troubleshooting

Installation Guide

WB36TL_50TL-IEN102011

81

5. Use a Multimeter to ensure that all of the varistors

in the installed state have a conducting connection
between connectors B and C.

CAUTION!
Electrostatic discharges can damage the inverter.

Components on the inside of the inverter may be irreparably damaged due to electrostatic
discharge.

• Ground yourself before touching a component.

Position of Varistors
See the following illustration to determine the position of the varistors.
Observe the following allocation of the
terminals:

• Terminal A: outer terminal

(Varistor connection with loop [crimp])

• Terminal B: middle terminal
• Terminal C: outer terminal

(Varistor connection without loop
[crimp])

Event

Action

☑ There is a conductive connection. There is probably a different fault in the inverter.

• Continue with point 9.
• Contact the SMA Serviceline (see

section 15 ”Accessories” (page 91)).