Electrical Connection
SMA Solar Technology AG
44
WB36TL_50TL-IEN102011
Installation Guide
5.6 Communication
Communication via Bluetooth with a communication device is activated as standard. Networking via
Bluetooth with other inverters is deactivated ex works.
The following setting options are possible via a rotary switch.
In order to restrict communication via Bluetooth between the inverters of your system and those of
neighboring systems, you can assign an individual NetID to the inverters of your system
(switch position 2 … F). This, however, is only necessary if neighboring systems are within a radius
of 500 m.
So that all inverters in your system are detected by your communication device, all inverters must have
the same NetID.
Procedure
1. Disconnect the inverter as described in section 7.2 ”Disconnect the device from voltage
2. Set the arrow on the rotary switches to the required
position using a screwdriver (2.5 mm).
3. Re-commission the inverter as described in
section 8 ”Restarting the system” (page 62).
Switch position
(NetID)
Setting
0
Off
1
Communication via Bluetooth with communication device possible, no
networking with other inverters (factory setting)
2 … F
Networking with other inverters
Acceptance of settings
The Bluetooth settings will only be activated after the line circuit breaker has been switched
on, the Windy Boy Protection Box connected and the Electronic Solar Switch plugged in.