3

< Grid fault >
The average grid voltage over 10 minutes
is no longer within the permissible range.
This can have the following causes:

• The grid voltage at the point of

connection of the inverter is too high.

• Grid impedance at the terminal of the

inverter is too high.

The inverter disconnects to assure
compliance with the voltage quality of the
grid.

• Check the grid voltage at the point of

connection of the inverter:

If due to local grid conditions the grid
voltage exceeds the configured limiting
value, ask the utility operator whether the
voltage can be adjusted at the feed-in
point, or whether he will agree to a
modification of the limiting value for
voltage quality monitoring.
If the grid voltage is continually within the
acceptable range, and this error is still
displayed, contact the SMA Serviceline.

4

< Grid fault >
The inverter has left the grid parallel
operation and for safety reasons
interrupted feeding-in.

• Check the power supply line for

strong, short-term frequency
variations.

5

< Grid fault >
The grid frequency is not within the
permissible range. For safety reasons, the
inverter disconnects itself from the grid.

• If possible, check the grid frequency

and observe how often major
deviations occur.

If repeated frequency variations occur and
as a result this error occurs, ask the grid
operator if it would agree to modify the
operating parameter.
Discuss the proposed parameters with the
SMA Serviceline.

6

< Grid fault >
The internal inverter monitoring has
detected an impermissibly high proportion
of direct current in the grid current.

• Check the power supply line for

direct current.

• If this is a recurrent phenomenon,

check with the grid operator whether
it is possible to raise the limiting value
of monitoring.

7

< Frq. not permitted >
The grid frequency has left the allowable
range. For safety reasons, the inverter
disconnects itself from the grid.

• As far as possible, check the grid

frequency and observe how often
major fluctuations occur.

If repeated frequency variations occur and
as a result this error occurs, ask the grid
operator if it would agree to modify the
operating parameter.
Discuss the proposed parameters with the
SMA Serviceline.

Event no. Cause

Corrective measures