SMA WB 3600TL User Manual
Page 31

SMA Solar Technology AG
Electrical Connection
Installation Guide
WB36TL_50TL-IEN102011
31
12. Connect L, N and protective conductor (PE) to the
AC terminal in accordance with the labels.
To do this, the insulated PE conductor must be 5 mm
longer than the insulated L and N conductors!
L and N must not be swapped.
13. Close all terminals of the AC terminal again until they snap into place.
14. Fold display down again and screw in place.
15. Tighten the lock nut firmly to the cable gland.
☑ The inverter is now connected to the power distribution grid (AC).
CAUTION!
Danger of crushing when terminals snap shut.
The terminals close by snapping down fast and hard.
• Press the terminals down with your thumb, do not grip the entire terminal on all sides.
• Keep fingers away from the terminals.
DANGER!
Danger to life due to high voltages in the inverter.
• Do not switch on the line circuit breaker until the small wind turbine system has been
connected and the inverter is securely closed.