Electrical Connection

Installation Guide

WB36TL_50TL-IEN102011

27

Cable requirements

Load Disconnection Unit

You must install a separate line circuit breaker for each inverter in order to ensure that the inverter
can be securely disconnected under load. The maximum permissible rating is located in
section 14 ”Technical Data” (page 85).
Detailed information and examples for the rating of a line circuit breaker can be found in the Technical
Information "Line Circuit Breaker" in the SMA Solar Technology AG download area at
www.SMA.de/en.

Object

Description

value

A

External diameter

12 mm … 25 mm

B

Cross section of insulated conductor

max. 10 mm²

C

Strip insulation

Approx. 12 mm

DANGER!
Danger to life due to fire.

When more than one inverter is connected to the same line circuit breaker, the protective
function of the line circuit breaker is no longer guaranteed. It can result in a cable fire or
the destruction of the inverter.

• Never connect several inverters to the same line circuit breaker.
• Comply with the maximum permissible fuse protection of the inverter when selecting

the line circuit breaker.