Electrical Connection

SMA Solar Technology AG

40

WB36TL_50TL-IEN102011

Installation Guide

The last change (executed via switch or communication device) is always verified and activated if
applicable. Consequently, the switch position may not necessarily show the actual country
configuration.

5.5.1 Checking the Country Standard

Check whether the inverter is set to the installation country.

1. Check that the country standard is correct on the basis of the display message during

(re‑)commissioning (see section 6 ”Initial start-up” (page 50) or section 8 ”Restarting the
system” (page 62))
or by means of the "SMA grid guard" measuring channel via a
communication device.

2. If necessary, change the setting via the parameter "CntrySet" and / or "Set country standard"

using the communication device or the rotary switches (see section 5.5.2 ”Setting the Country
Standard and Language using Rotary Switches” (page 43)) accord
ing to the following table.

The settings of each country data set are specified in the operation parameters. The parameters can
be read out using a communication device. The description of the operating parameter is available
in the download area at www.SMA.de/en in the category "Technical Description" of the respective
inverter.

Changing of parameters in grid guard protected country data sets
If the parameters within protected country data sets are changed, these are no longer
protected and instead of the standard, "ADJ" or "Special setting" is displayed. In this case,
the parameters are not changed automatically after 10 grid-feed hours, but have to be
manually locked. To manually lock the parameters, set the SMA Grid Guard Code to
"54321".

Further information on parameter settings
Detailed information on how to proceed with respect to setting and changing parameters
is available in the respective user manual for your software.

Display language
Once you have set the country standard, you can set the display language at any time
using rotary switch B. However, you have to then set the rotary switch A to "0" in order to
keep the country data set.

(A) (B) Country data set

Display language

Grid guard
protection

Country

0

0

Delivery state

Delivery state

Dependent on
parameter set

Dependent on
parameter set

0

1

Retained

English

Dependent on
parameter set

Dependent on
parameter set

0

2

Retained

German

Dependent on
parameter set

Dependent on
parameter set