5.3 Connection to the Power Distribution Grid (AC)

5.3.1 Conditions for the AC Connection

Observe all connection conditions of the utility operator for connecting to the power distribution grid!

Residual current breaker

The inverter is equipped with an integrated universal current sensitive residual-current monitoring unit.
The inverter can automatically differ between real fault currents and "normal" capacitive leakage
currents.
If an external RCD or residual current breaker is strictly required, you must use a switch that triggers
at a failure current of 100 mA or higher.

Cable Sizing

The grid impedance of the AC cable must not exceed 1 Ohm. Otherwise, the inverter will disconnect
at full feed capacity due to excessive voltage at the feed-in point.
The wire cross-section should be dimensioned so output losses do not exceed 1 % at nominal power.
The maximum cable lengths depending on the wire diameter are displayed in the following table.

The conductor cross-sectional area required in individual cases depends on the following factors,
among others:

• Ambient temperature,
• Routing method,
• UV resistance,
• Conduction losses,
• valid installation requirements of the respective country (installation location).

Cross section of insulated
conductor

Maximum wire length

WB 3600TL

WB 5000TL

6.0 mm²

23.3 m

18.6 m

10.0 mm²

38.8 m

31.1 m