SMA WB 3600TL User Manual
Page 30

Electrical Connection
SMA Solar Technology AG
30
WB36TL_50TL-IEN102011
Installation Guide
8. Loosen the screw if the display until it can be flipped
upward to facilitate connection.
Flip up the display until it clicks into place.
9. Undo the lock not of the AC cable gland and
remove the filler plug from the cable gland.
10. Pull the cable through.
11. Open all AC terminals.
Seal in the AC cable gland
There is a two-part seal in the cable gland.
Remove the inner insert of the seal if required.
This is necessary to route a thicker cable.
The following guideline values apply:
• Cable diameter with seal and insert: 12 mm … 16 mm
• Cable diameter with seal without insert: 15 mm … 21 mm
CAUTION!
Risk of fire when connecting two wires to one terminal.
If 2 wires are connected to one terminal, a poor electrical contact can result in overheating
or a risk of fire.
• Never connect more than one conductor per terminal.