beautypg.com

Measurement Computing StrainBook/616 User Manual

Page 19

background image

Using a Sample for Triggering

TTL-level Triggering

StrainBook includes TTL-level triggering through the digital I/O port. A detailed discussion of triggering

begins on page 4-7.

Sync Ports

StrainBook includes two SYNC ports. Up to four StrainBooks can be scan-synchronized and triggered by

connecting one of the two SYNC ports of a unit to a SYNC port on a second StrainBook. StrainBooks can

also be connected in this manner to a SYNC port on a WBK40 or WBK41 module.
Additional information on synchronization begins on page 4-8.

Control, Timing, and Signal Processing

At each sample time, the DSP: (a) reads from the scan sequence table, and (b) accordingly programs a

Control-and-Timing Circuit for the next sample. The Control-and-Timing Circuit waits precisely until the

start of the next sample, then selects:

the input channel

PGA gain

level-shifter offset

A/D input source

The control-and-timing circuit conveys this information to any attached expansion units and precisely

controls the A/D conversion timing.
An EEPROM holds the calibration information needed for real-time sample correction.
The digital I/O port is read and written by the Digital Signal Processor to transfer bytes of digital data.

It may be used as a simple 8-bit input port or as a 32-address byte-wide I/O port.

StrainBooks and the Ethernet, General Information

The most common and highest-performance Ethernet connection for StrainBook is achieved via a

dedicated, point-to-point Ethernet link between the PC and the unit’s Ethernet port. Data transfer rates

in this configuration will accommodate continuous 1 Mreading/sec transfers from the StrainBook to the

PC.
With an enterprise-wide Ethernet network connection, any number of StrainBooks can be connected to the

network. Enterprise-wide Ethernet networks are typically shared amongst a large number of devices. In

such a scenario, the data transfer rates from the StrainBook are dependent on other network traffic at the

time of data transfer.

If you need to have continuous, 1 Mreading/s transfers from the StrainBook, you should

avoid connecting StrainBooks to an enterprise-wide Ethernet network. However, to

improve the data transfer performance of StrainBooks that are connected to such a

network, a factory-installed WBK30 memory option should be employed. Contact the

factory for additional information.


Up to four StrainBooks can be synchronized to each other via their SYNC ports. Each unit has two

identical SYNC ports. Either or both SYNC ports can be used to connect to the units via SYNC cables

CA-74-1 or CA-74-5 (1-foot or 5-foot cables, respectively). The units can be scan-synchronized and

triggered from any other SYNC-connected unit. The StrainBooks are individually connected to the

Ethernet, as indicated in the following figure.
This application is useful when the channel requirements exceed the 64 channel capability of one

StrainBook. It is also useful when the per-channel bandwidth exceeds that which could be accomplished

by a lone StrainBook, or if multiple time bases are required.

StrainBook/616

967794

Operation Reference 2-5

This manual is related to the following products: