CFN II Quick Reference
C09159 Rev. 2238
47
Cabling - over 8 feet
Cabling the TLS-350 for Tank/Level Data
The TLS may be connected on either the Console or
Island loop. If a connection has not already been
provided for the TLS, use the Island Loop.
TLS 350R
1. RS-232 Security Code: 000001
2. RS-232 End of Message: Enabled
System Requirements
Console must have “Send All Messages Feature”
Non-blended dispensers are supported
All Profit Point Broadcast Messaging enabled
Gasboy Junction Box P/N C05020
Interface Module Hardware Configuration.
Baud
Rate
DATA
Bits
CFN
Parity
SW1
SW2
9600
8
none *
all open
all open
9600 7 even
1-3=closed
4=open
all open
9600 7 odd
1,2,4=closed
3=open
all open
* default
Cabling the TLS-350R for with BIR
The TLS must be connected on the Console Loop to
receive BIR data.
ECPU Board Battery Switch ON (SW1)
HRM Features (Europe Only) - Enabled
(DIP Switch 3 in the Closed position)
Other areas - disabled
(DIP Switch 3 in the OPEN position)
RS-232 Security Code-Disabled
(DIP Switch 2 in the OPEN position)
Front Panel Security Code - Disabled
(DIP Switch 1 in the OPEN position)
DIP rocker switches
OPEN=open end down, num. up
CLOSED=open end up, num. down
DIP rocker switch 4 - Unused
Battery Backup Switch - OFF (down)
Wiring to the Junction Box
Note: if cable must be shortened, remove excess at
the TLS end.
For further installation instructions, refer to the
VeederRoot manual titled “Gasboy CFN TLS-
350/TLS-350R Systems Setup.”
EECO tank monitor
Interface with CFN II or CFN III using either the a
RS232 connection utilizing the CFN System’s PORT
command or a Gasboy RS232-RS485 converter. In
the EECO monitor setup menus, there are two
selections for connecting to a site controller. These
are: Gasboy-PC or Gasboy-Site Control.
Gasboy-PC
Use this setting when connecting to one of the site’s
RS232 ports and interfacing using the PORT
command. This sets the communication parameters to
9600, odd, 1 stop bit, 7 data bits, and no security
code.
Gasboy-Site Control
Use this setting when connecting to one of the site's
RS-485 Junction Box
(PC C05020)
1 2 3 4 5
GND
GND
TX+
RX-
TX- RX+
Cable
AC GND
Blue/White Stripe
White/Blue Stripe
Orange/White Stripe
White/Orange Stripe
1 2 3 4 5
GND
GND
TX+
RX+
TX-
RX-
TLS-350R
Blue/White Stripe
White/Blue Stripe
Orange/White Stripe
White/Orange Stripe
Inside Connector
Terminal Block
inside Junction Box