CFN II Quick Reference

C09159 Rev. 2238

47

Cabling - over 8 feet

Cabling the TLS-350 for Tank/Level Data

The TLS may be connected on either the Console or
Island loop. If a connection has not already been
provided for the TLS, use the Island Loop.

TLS 350R

1. RS-232 Security Code: 000001

2. RS-232 End of Message: Enabled

System Requirements

Console must have “Send All Messages Feature”

Non-blended dispensers are supported

All Profit Point Broadcast Messaging enabled

Gasboy Junction Box P/N C05020

Interface Module Hardware Configuration.

Baud

Rate

DATA

Bits

CFN

Parity

SW1

SW2

9600

8

none *

all open

all open

9600 7 even

1-3=closed

4=open

all open

9600 7 odd

1,2,4=closed

3=open

all open

* default

Cabling the TLS-350R for with BIR

The TLS must be connected on the Console Loop to
receive BIR data.

ECPU Board Battery Switch ON (SW1)

HRM Features (Europe Only) - Enabled

(DIP Switch 3 in the Closed position)

Other areas - disabled

(DIP Switch 3 in the OPEN position)

RS-232 Security Code-Disabled

(DIP Switch 2 in the OPEN position)

Front Panel Security Code - Disabled

(DIP Switch 1 in the OPEN position)

DIP rocker switches

OPEN=open end down, num. up
CLOSED=open end up, num. down

DIP rocker switch 4 - Unused

Battery Backup Switch - OFF (down)

Wiring to the Junction Box

Note: if cable must be shortened, remove excess at
the TLS end.

For further installation instructions, refer to the
VeederRoot manual titled “Gasboy CFN TLS-
350/TLS-350R Systems Setup
.”

EECO tank monitor

Interface with CFN II or CFN III using either the a
RS232 connection utilizing the CFN System’s PORT
command or a Gasboy RS232-RS485 converter. In
the EECO monitor setup menus, there are two
selections for connecting to a site controller. These
are: Gasboy-PC or Gasboy-Site Control.

Gasboy-PC

Use this setting when connecting to one of the site’s
RS232 ports and interfacing using the PORT
command. This sets the communication parameters to
9600, odd, 1 stop bit, 7 data bits, and no security
code.

Gasboy-Site Control

Use this setting when connecting to one of the site's

RS-485 Junction Box

(PC C05020)

1 2 3 4 5

GND

GND

TX+

RX-

TX- RX+

Cable

AC GND

Blue/White Stripe

White/Blue Stripe

Orange/White Stripe

White/Orange Stripe

1 2 3 4 5

GND

GND

TX+

RX+

TX-

RX-

TLS-350R

Blue/White Stripe

White/Blue Stripe

Orange/White Stripe

White/Orange Stripe

Inside Connector

Terminal Block

inside Junction Box