CFN II Quick Reference

44

C09159 Rev. 2238

23 — Wayne 3 product blender, hoses 1, 3, and 5.
For Wayne products V580 and V590U. Previously
these pumps required using 5 hoses, setting the price
code for hoses 2 & 4 to 99. With this option, only
define 3 hoses and the Wayne driver maps to the
appropriate pump positions automatically.

Tokheim Pump Programming

Mode 19 - set dispenser function code to 0.

Mode 23 - set address (1-16), number of products,
number of sides, and number of prices.

Mode 25 - set price-change mode equal to 1.

Mode 26 - on the Premier should be set as 1.

Site Controller II K2 Jumper Settings

In the Site Controller II section (earlier in this
manual) see the jumper drawings under CPU Board.

Gilbarco Interface Unit

Part number: C05688. Use a C04500 cable from the
RS422/RS485 junction box to the RS422 port of the
interface unit.

Use Gilbarco firmware version 70.2 or later. Product
authorization does not work with Gilbarco pumps
before version 2.0c of Gasboy’s interface firmware
and version 2.0cp2 of the Site Controller II software.

Interface
Terminal

Short
Wire
Color

Terminal Block
Connection

Field
Wire
Color

Gilbarco
dist. Box

Terminal
Legend

P1-1

red

1+ (top terminal) black box

1

-BLK

P1-2

black

1- (next down)

red

box 1

+RED

P2-1

red

2+

(third

down) black box

2

-

BLK

P2-2

black

2- (bottom)

red

box 2

+ RED

CPU Board

Jumper

Function and/or Normal Setting

K1

All K1 jumpers are absent.

K2

All K2 jumpers are absent.

K3

Position 1: enables the dead man timer.
K3-1 jumper must be installed.
K3-1 is the pair of K3 terminals closest to P9, the
long double-row offboard connector at the edge
of the board.
Position 2: K3-2 jumper is absent. K3-2 is the
pair of K3 terminals farthest from P9.

K4 ----

K5

Battery to U31; must install.

K6

Battery to U32; must install.

K7

Enables the AC power fail circuit; must install.

K8

K8 jumper is absent.

DIP Switch Bank 2. This switch sets the poll address
and allows memory to be cleared.

Position & Definition

Setting(*=customary)

1 debug

mode

*closed=normal mode
open=debug mode

2

erase memory on reset

*closed=no
open=yes

3-8

interface address

see next table

Address

2-3

2-4

2-5

2-6

2-7

2-8

1 cl cl cl cl cl cl

2 cl cl cl cl cl op

3 cl cl cl cl op cl

4 cl cl cl cl op op

5 cl cl cl op cl cl

.

.

.

64 op op op op op op

DIP Switch Bank 3

Position & Definition

Setting(*=customary)

1-2

local terminal baud rate

*open=9600

(also see below)

3

CRIND

open=RS-422 to CRIND

closed=current loop

4

reports (see below)

open=onhook activate

closed=no report

5

product authorization

open= no restrictions

closed=restrict grades

Switch 3-4: with Site Controller versions before 2.0b,
pumps are deactivated if offhook, and activated if
onhook. This is the sequence reported with push-to-
start and cash-credit.

Baud Rate

3-1

3-2

9600 open open

2400 open closed

1200 closed open

300 closed

closed

DIP Switch Bank 4. This switch selects certain price
level options and allows either twelve or sixteen
pumps (six or eight double-sided units) on a loop.