C09159 Rev. 2238

39

Pump Control

Unit

EXPMUX CPU Board

Part number: C05837

LEDs

LED

Color

Function

DL1 green

reset

high

DL2 green

battery

okay

DL3 red

422

receive

DL4 red

422

transmit

DL5, 8, 11, 14

red

slow flow, pump 1, 2, 3, 4

DL6, 9, 12, 15

red

fast flow, pump 1, 2, 3, 4

DL7, 10, 13, 16

red

submersible, pump 1, 2, 3, 4

Switches

DIP switch banks B and C on the EXPMUX CPU
board set options latched in at power-up time:

DIP Switch Bank B

Position & Definition

Setting(*=customary)

1-4 address

see

below

5 pulser

type

closed

6-8 relay

closed

Address

B-1

B-2

B-3

B-4

1

cl

cl

cl

cl

2

op

cl

cl

cl

3

cl

op

cl

cl

4

op

op

cl

cl

5

cl

cl

op

cl

6

op

cl

op

cl

7

cl

op

op

cl

8

op

op

op

cl

9

cl

cl

cl

op

10

op

cl

cl

op

11

cl

op

cl

op

12

op

op

cl

op

13

cl

cl

op

op

14

op

cl

op

op

15

cl

op

op

op

16

op

op

op

op

DIP Switch Bank C

Position & Definition

Setting(*=customary)

1-4

pulser enabled (pumps 1-4)

(see note below)

closed=after reset is

complete

open=upon activation

5 ____

6

dead man timer

*always open=enabled

7 ____

8 test

mode

*closed=no

open=yes

Note: In connection with pulser enabled, there are
two error codes, each with three characters, that can
show up in the error column on a transaction printout.
The reset-failed-to-start transaction code is $D2
through $DF, and the reset-failed-to-complete
transaction code is $E5 through $EF ($ indicates
hexadecimal). The last character in each code (2
through F or 5 through F) is the number of seconds
the PCU waited for reset to start or complete. This
numeric character is incremented by one each time
the PCU reset-to-start/complete times out, until the
maximum timeout of 15 (15 is F in hexadecimal
counting) seconds is reached.

Test Mode. When test mode is activated with switch
C-8, switch C-5 determines the relay limits:

C-5

Function

open

pump slows at 500 pulses and turns off at 510 pulses

closed

pump slows at 50 pulses and turns off at 60 pulses

In test mode, switches C-6 and C-7 select the pump
to be tested:

Pump to Test

C-6

C-7

1 closed

closed

2 open

closed

3 closed

open

4 open

open

Jumpers

Jumper Setting

Setting

Default

K1 installed=battery

connected

removed=battery

disconnected

installed