beautypg.com

Tank gauge, Veeder-root cpu board – Gasboy CFN Series CFN II Quick Reference User Manual

Page 50

background image

CFN II Quick Reference

46

C09159 Rev. 2238

selection to work.

all Wayne dispensers must be configured in
sequential, consecutive order. All Wayne
dispensers must be addressed as starting with
number 1, regardless of the actual pump numbers
that they are configured with in the Site
Controller.

in the Wayne Data Distribution Box, any
switches that are not wired to a dispenser must
be in the Bypass position.

For non-blenders:

each hose must be assigned a price code in
ranges 1-5, 11-15, 21-25, 31-35; all hoses on a
pump must be in the same decade.

For all blenders:

use price codes 6-9, 16-19, 26-29, 36-39 for
blended hoses. Use price codes 4, 14, 24, 34 for
low feedstock (non-blended hoses). Use price
codes 5, 15, 25, 35 for high feedstock (non-
blended hoses).

product names for products in blended hoses
should contain blend rate (for example, blended
40%
, using a percent sign); do not use a percent
sign in non-blended hoses.

For fixed blenders:

hose 1 is always a non-blended, low-feedstock
hose and must have price code 4 (or 14 or 24 or
34). Hose 3 is always a non-blended, high-feed-
stock hose and must have price code 5 (or 15 or
25 or 35). Hose 2 is the blended hose and must
have a price code in ranges 6-9, 16-19, 26-29,
36-39.

For variable 5-product blenders:

hoses 1-5 must use price codes 4-9, 14-19, 24-
29, 34-39, with no repeats.

For variable 3-product blenders:

assign 5 hoses, but assign price code 99 to hoses
2 and 4 since the system uses only hoses 1, 3,
and 5.

SC II Pump Configuration

In the PUMP configuration program, in submenu 3,
set the following options:

Wayne type

Options to set

MPD 1,2,5,7,9

MPD $/Cr

1,2,3,5,7,9

Blender 1,2,5,7,9,12

Blender $/Cr

1,2,3,5,7,9,12

Tank Gauge

Veeder-Root CPU Board

TLS 250 and TLS 250i

DIP Switch Bank 1

Position & Definition

Setting(*=customary)

1-3 interboard

communications

*always

closed

4 parity:

before

ver.

1.0H

ver 1.0H & later


*always open-even
*always closed=odd

5 security

code

*always

closed=enable

The charts below apply to version 23 and above,
option PCB, for TLS 250; and version 12 and above,
option PCB for TLS 250i.

CFN II versions below 1.0 H

9600, even

Enable Security Code:

Yes

Tank Monitor Address:

000001 (assumes only

one monitor on system)

EoT Character:

Enable

CFN II version 1.0 H and above

9600, odd
Enable Security Code:

Yes

Tank Monitor Address:

000001 (assumes only

one monitor on system)

EoT Character:

Enable

TLS 350

9600, odd, 1 stop bit, 7 data bits

Enable Security Code:

Yes

Auto Transmit Message: Disabled
Tank Monitor Address:

000001 (assumes only

one monitor on system)

EoT Character:

Enable

Cabling - 8 feet or less