Tank gauge, Veeder-root cpu board – Gasboy CFN Series CFN II Quick Reference User Manual
Page 50

CFN II Quick Reference
46
C09159 Rev. 2238
selection to work.
•
all Wayne dispensers must be configured in
sequential, consecutive order. All Wayne
dispensers must be addressed as starting with
number 1, regardless of the actual pump numbers
that they are configured with in the Site
Controller.
•
in the Wayne Data Distribution Box, any
switches that are not wired to a dispenser must
be in the Bypass position.
For non-blenders:
•
each hose must be assigned a price code in
ranges 1-5, 11-15, 21-25, 31-35; all hoses on a
pump must be in the same decade.
For all blenders:
•
use price codes 6-9, 16-19, 26-29, 36-39 for
blended hoses. Use price codes 4, 14, 24, 34 for
low feedstock (non-blended hoses). Use price
codes 5, 15, 25, 35 for high feedstock (non-
blended hoses).
•
product names for products in blended hoses
should contain blend rate (for example, blended
40%, using a percent sign); do not use a percent
sign in non-blended hoses.
For fixed blenders:
•
hose 1 is always a non-blended, low-feedstock
hose and must have price code 4 (or 14 or 24 or
34). Hose 3 is always a non-blended, high-feed-
stock hose and must have price code 5 (or 15 or
25 or 35). Hose 2 is the blended hose and must
have a price code in ranges 6-9, 16-19, 26-29,
36-39.
For variable 5-product blenders:
•
hoses 1-5 must use price codes 4-9, 14-19, 24-
29, 34-39, with no repeats.
For variable 3-product blenders:
•
assign 5 hoses, but assign price code 99 to hoses
2 and 4 since the system uses only hoses 1, 3,
and 5.
SC II Pump Configuration
In the PUMP configuration program, in submenu 3,
set the following options:
Wayne type
Options to set
MPD 1,2,5,7,9
MPD $/Cr
1,2,3,5,7,9
Blender 1,2,5,7,9,12
Blender $/Cr
1,2,3,5,7,9,12
Tank Gauge
Veeder-Root CPU Board
TLS 250 and TLS 250i
DIP Switch Bank 1
Position & Definition
Setting(*=customary)
1-3 interboard
communications
*always
closed
4 parity:
before
ver.
1.0H
ver 1.0H & later
*always open-even
*always closed=odd
5 security
code
*always
closed=enable
The charts below apply to version 23 and above,
option PCB, for TLS 250; and version 12 and above,
option PCB for TLS 250i.
CFN II versions below 1.0 H
9600, even
Enable Security Code:
Yes
Tank Monitor Address:
000001 (assumes only
one monitor on system)
EoT Character:
Enable
CFN II version 1.0 H and above
9600, odd
Enable Security Code:
Yes
Tank Monitor Address:
000001 (assumes only
one monitor on system)
EoT Character:
Enable
TLS 350
9600, odd, 1 stop bit, 7 data bits
Enable Security Code:
Yes
Auto Transmit Message: Disabled
Tank Monitor Address:
000001 (assumes only
one monitor on system)
EoT Character:
Enable
Cabling - 8 feet or less