User define error – ATEIS IDA8C User Manual
Page 91

Product Features
91
© 2012 ATEÏS
o G. Fault LED on front panel of IDA8C/S.
Log
Text messages display at touch screen on front panel of IDA8C:
"Fireman Error"
"Fireman Audio Open"
Text message display at window [Machine Fault Record] of Ateis Studio:
Buzzer sound output to monitoring speaker on front panel of IDA8C.
Fault Handling
Observe link and active LED indicator on RJ45 connector of PC with VOX@NET server installed and
ethernet switch, it is error if link LED is not light up or active LEC isn't blinking. possible cases are
listed below:
Both switch and PC get wrong LED display behavior, check cable between PC & ethernet
swich.
Only VOX@NET get wrong LED display behavior, check network card of PC, you can change
a network card to see if it is working.
Only switch get wrong LED display behavior, check switch, you can simply change to another
port to see if it is working.
Observe link and active LED indicator on RJ45 connector of IDA8C/S and switch, possible cases are
listed below:
Both switch and IDA8C/S get wrong LED display behavior, check cable between IDA8C/S &
ethernet swich.
Only IDA8C/S get wrong LED display behavior, check IDA8C/S, you can replace it by a good
IDA8C/S to see if it is working.
Only switch get wrong LED display behavior, check switch, you can simply change to another
port to see if it is working.
4.1.6.2.8 User Define Error
Fault Meaning
A user define error is detected by IDA8C/S, this kind of error can be defined using "Fault Definer"
DSP component.
Fault Indication
LED Indicator
When this error is detected, following LEDs will light up: