To determine the boundary of fault detection for selected zone. There is a fault recognized if one
of follow conditions is true:
Measure < (Full Loaded Reference x (100% - Tolerance%))
Measure > (Unloaded Reference x (100% + Tolerance%))
Get Reference
Get the reference values of selected zone for further fault detection. Be aware, hardware
configuration(IDA8C/S, amplifiers, wiring) should be done before get reference.
Reset Reference
Clear reference values of selected zone to go back initial status. if reference value is cleared,
monitoring will be stopped.
Measurement
After parameter settings are done in lower part grid, IDA8C/S start to measure value get from internal
circuit, and display it on the grid at upper part of window:
Unloaded Reference
Display the value of unloaded reference which is the gain of amplifier when there is no load to
the zone. This value use to determine if there is a fault of normal amplifier or not.
Full Loaded Reference
Display the value of full loaded reference which is the gain of amplifier when there is full load to
the zone. This value use to determine if there is a fault of normal amplifier or not.
Measure
Display the value of measured which is the gain of amplifier.