7.2 General

This section describes the suggested maintenance and troubleshooting procedures. The
troubleshooting procedure is divided into two sections. The first section deals with basic
operation and connection of the equipment. The second section requires opening the unit and
using the LED indicators and a simple multimeter to troubleshoot the unit down to the module
level. Only a qualified electronic technician should attempt this level troubleshooting.

7.3 Basic operation

Table 7-1: Basic Symptoms

PARAGRAPH

PROBLEM

7.3.1

Excessive Output Voltage

7.3.2

Poor Output Voltage Regulation

7.3.3

Overload Light On

7.3.4

Distorted Output

7.3.5

Unit Shuts Down After 1-2 Seconds

7.3.6

No Output and no lights on front panel

7.3.7

No output but “power on” LED on front panel is lit.

7.3.1 Excessive Output Voltage

CAUSE

SOLUTION

External sense not connected

Connect the external sense to the AC
power outlet TB2.

7.3.2 Poor Output Voltage Regulation

CAUSE

SOLUTION

Unit is overloaded

Remove overload

Unit is programmed to wrong voltage
range.

Select correct voltage range.

Input line has fallen below spec. limit.

Check supply voltage.

7.3.3 Overload Light is On

CAUSE

SOLUTION

Unit is overloaded

Remove overload

Unit is switched to high voltage range.

Select correct voltage range.

7.3.4 Distorted Output

CAUSE

SOLUTION

Power source is grossly overloaded.

Reduce load

The crest factor of the load exceeds 3:1 on
the low range or 5:1 on the high range.

Reduce load current peaks by reducing
load.