16awg/1.3mm “generic” cable specifications, Pvc. see, Section , 16awg/1.3mm “generic – Echelon FT 3150 Smart Transceiver User Manual
Page 132: Cable specifications

Appendix B - Qualified TP/FT-10 Cable Specifications and Sources
126
FT 3120 / FT 3150 Smart Transceiver Data Book
Table B.5 Worst-Pair Near-End Crosstalk (dB) Minimum
Values are shown for information only. The minimum near-end cross talk (NEXT) coupling loss for any pair com-
bination at room temperature is to be greater than the value determined using the formula
for all frequencies in
the range of 0.772MHz-20MHz for a length of 1000 feet:
NEXT (F
MHz)
>NEXT(0.772)-15*log(F
MHz
/0.772)
16AWG/1.3mm “Generic” Cable Specifications
The specifications for the 16AWG/1.3mm Generic cable qualified by Echelon for use with TP/FT-10 networks is
presented below. The generic single twisted pair is stranded (19 x 29) with tinned copper.
Table B.6 General Specifications
Table B.7 Attenuation and Propagation Delay Characteristics
Frequency
Crosstalk db
772kHz
58
1.0MHz
56
4.0MHz
47
8.0MHz
42
10.0MHz
41
16.0MHz
38
20.0MHz
36
Specification
Minimum
Typical
Maximum
Units
Condition
DC Resistance, each
conductor
14.0
14.7
15.5
/km
20°C per ASTM D
4566
DC Resistance Unbal-
ance
5%
20°C per ASTM D
4566
Mutual Capacitance
55.9
nF/km
Per ASTM D 4566
Characteristic Imped-
ance
92
100
108
_
64kHz to 1MHz, per
ASTM D 4566
Characteristic
Minimum
Typical
Maximum
Units
Condition
Attenuation
20kHz
64kHz
78kHz
156kHz
256kHz
512kHz
772kHz
1000kHz
1.3
1.9
2.2
3.0
4.8
8.1
11.3
13.7
dB/km
20°C per ASTM D 4566
Propagation Delay
5.6
ns/m
78kHz
Ω