Model 5600 Installation and Operation Manual

9-2

151450

2. If Silence/Reset Inhibit Enabled is selected in programming, that button and the

SYSTEM RESET button are ignored for the first 30 seconds of the first alarm or
supervisory signal

9.1.6

To Initiate a Fire Drill

1. Press Drill until “DRL” is displayed

2. Press SYSTEM RESET to end the drill

9.1.7

For a Dialer Test

Press JumpStart and Next at the same time

9.1.8

For a Lamp Test

Press JumpStart and Prev at the same time

9.1.9

AC LED

The AC LED will blink for the loss of AC and the Trouble Relay will activate after the
programmed delay time (default = 3 hours).

9.1.10 Walk Test

1. Press and hold Walk Test for about 5 seconds to start a walk test

2. Press SYSTEM RESET to end the test

9.1.11 Seven Segment Display

On the 7 segment display:

“AC1” indicates dialer account 1 failed to report

“AC2” indicates dialer account 2 failed to report

“dlr” indicates a problem with the dialer. The panel must be returned to the factory
for repair

“drL” indicates a fire drill is taking place

“Ln1” indicates low/no voltage on phone line 1

“Ln2” indicates low/no voltage on phone line 2

“CE1” indicates Autotest Comm Error Line 1

“CE2” indicates Autotest Comm Error Line 2

“SLC err” indicates an over current condition on the SLC loop

“bAt” indicates battery trouble