1 current draw worksheet for 5600 for ul 864 – SilentKnight 5600 User Manual
Page 27

Before You Begin Installing
151450
3-7
3.6.1.1 Current Draw Worksheet for 5600 for UL 864
Use Table 3-2 to determine amp-hour requirements during alarm/battery standby
operation. (Copy the page if additional space is required.) You can install up to 25
SLC devices and two 5635 Remote Annunciator.
Table 3-2: Current Calculation Worksheet for SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current
For each device use this formula: This column X This column = Current per number of
devices.
Fire Panel (Current draw from
battery)
1
Standby: 135 mA
135 mA
Alarm: 220 mA
220 mA
Accessory Modules
5635 Remote Annunicator
2
Standby: 37 mA
mA
Alarm: 40 mA
mA
Addressable SLC Detectors
HFS-P
(25 max.
detectors or
modules in
any combina-
tion)
Standby: 0.27 mA
Alarm: 6.5 mA
mA
mA
HFS-PT
mA
mA
HFS-D
mA
mA
HFS-T
mA
mA
SK-Photo
mA
mA
SK-Photo-T
mA
mA
SK-DUCT
mA
mA
SK-Heat
mA
mA
Addressable SLC Modules
HFS-MM
(25 max.
detectors or
modules in
any combina-
tion)
Standby/Alarm: .375 mA
mA
mA
SK-Pull-SA
Standby/Alarm: .375 mA
mA
mA
SK-PULL-DA
Standby/Alarm: .375 mA
mA
mA
HFS-MR
Standby/Alarm:
0.255mA
mA
mA
SK-Minimon
Standby/Alarm: .375 mA
mA
mA
SK-Relay
Standby/Alarm: .375 mA
mA
mA
SK-ISO
10 max.
Standby/Alarm: .45 mA
mA
mA
A
Total System Current
Auxiliary Devices
Refer to devices manual for current rating.
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
B
Auxiliary Devices Current
Notification Appliance Circuits
Refer to device manual for current rating.
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C
Notification Appliances Current
mA
D
Total current ratings of all devices in system (line A + line B + C)
mA
mA