Model 5600 Installation and Operation Manual

7-2

151450

7.6

Viewing Active Supervisory Points

When one or more SLC points within a zone are in supervisory alarm, the supervisory
LED for that zone will blink and outputs will activate that are mapped to supervisories
within the zone. To display the SLC address of an input point that is in supervisory,
press the SUPERVS ID key once and use the PREV (previous) or NEXT key to scroll
through the supervisory points. All points that are in supervisory spanning all zones
on the control panel will be displayed when using the scroll keys.

7.7

Viewing Active Trouble Points

When one or more SLC points within a zone are in trouble, the trouble LED for that
zone will blink and outputs will activate that are mapped to troubles within the zone.
To display the SLC address of an input point that is in trouble, press the TROUBLE ID
key once and use the PREV (previous) or NEXT key to scroll through the trouble
points. All addressable points that are in trouble throughout the control panel will be
displayed when using the scroll keys.

Note: If there are any system level troubles active, the LED corresponding to the system level trouble

will blink also. However, system level troubles are not displayed on the 7 segment display after
using the TROUBLE ID key and the PREV or NEXT to scroll addressable troubles. Only point
troubles are displayed.

7.8

Walk Test

Walk test is enabled by holding the WALK TEST key until the PZT stops. This takes
about 5 seconds. Once in walk test the 7 segment display will show that the walk test
is active. During walk test, inputs can be activated and the outputs that are mapped to
the input will be activated for 3 seconds. The input will automatically be reset when
the outputs are deactivated.

The exit walk test, hold the WALK TEST key until the PZT stops. The panel is now in
normal standby mode.

7.9

Fire Drill

A fire drill is activated by holding the DRILL key until the 7 segment display shows drl
on. All outputs will be active. To stop the fire drill, press the RESET key. If the reset
key is not pressed within 10 minutes, the fire drill will automatically reset.