Section 6 programming, 1 ul 864 programming requirements, Ul 864 programming requirements – SilentKnight 5600 User Manual
Page 63

151450
6-1
Section 6
Programming
This section of the manual describes how to change the control panel programming
options from the built-in web page of the control panel. All options described in this
section are edited via the panel’s built in web page
6.1
UL 864 Programming Requirements
*Only needs to be enabled if using the DACT.
Important!
Before any customized programming is done, JumpStart should be run first. After
JumpStart is run, thoroughly test the system. The reason the system should be
tested after JumpStart is because JumpStart automatically programs the system,
searching for and configuring all SLC devices and SBUS annunciators it finds.
JumpStart allows you to confirm the integrity of the installation prior to performing
any custom programming. After determining that the hardware is properly installed,
custom programming can be performed. Refer to Section 6.
Table 6-1: Standards in Requirements for Control Units and Accessories
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES: This product incorporates field programmable software.
In order for the product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming features or
options must be limited to specific values or not used at all as indicated below.
Programming Option
Menu Item
Permitted in
UL 864 (Y/N)
Possible
Settings
Settings
Permitted in UL
864
System Options
Low AC Report
Delay
Yes
0–30 hours
1–3
Zone Options
Supervisory
Yes
Latching/Non
Latching
Zone Options
Waterflow
Yes
Latching/Non
Latching
System Options
Alarm Verification
Yes
1-250 seconds
60-250 seconds
Dialer Phone line Programming
option
Line Monitor
Enabled
Yes
Y/N
Y*