Control Panel Installation

151450

4-11

Wiring Distance calculation example:

Suppose a system is configured with the following SBUS modules:

1 - Module 5635 Fire Annunciator

The total worst case current is calculated as follows:

Using this value, and referring to the Wiring Distance table, it can be found that the
available options are:

1852 feet maximum using 22 Gauge wire

4688 feet maximum using 18 Gauge wire

6000 feet maximum using 16 Gauge wire

6000 feet maximum using 14 Gauge wire

5635 Current Draw

= 1 x .04 amps

= .04 amps

Total Worst Case Current Draw

= .04 amps