11 remote station applications, 1 city box connection using the 5220 module – SilentKnight 5600 User Manual
Page 54

Model 5600 Installation and Operation Manual
4-22
151450
4.11 Remote Station Applications
4.11.1 City Box Connection Using the 5220 Module
This section describes how to connect the control panel to a municipal fire alarm box
or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire
alarm service. The city (master) box is an enclosure that contains a manually
operated transmitter used to send an alarm to the municipal communication center
which houses the central operating part of the fire alarm system.
City Box Standby Current:
0 (Notification supervision current
accounted for in control panel draw.)
Alarm Current:
1 Amp for 1 second
Max Voltage:
24 VDC
The maximum coil and wire resistance (combined) must not exceed 30 ohms.
To install the 5220 for city box connection:
1. Use one of the knockouts on the right side of the control panel to connect the
5220 using a short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel as shown in Figure 4-17. This drawing also
shows how to connect the city box coil to terminals 3 and 4 on the 5220. Do not
install an EOL resistor in the terminals of the NAC circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program NAC1 as auxiliary and power constant on. Program NAC2 as a non-
silencing, constant on notification circuit.