4.10 On-Board Relays (Conventional, Power Limited)
The control panel has two built-in programmable relays and a built-in trouble relay. All
relays are Form C rated at 2.5 A @ 24 VDC Resistive.
4.10.1 Common Trouble Relay
The control panel has a dedicated Form C trouble relay built into terminals labeled
TROUBLE. The relay provides a normally open and a normally closed contact. The
trouble relay will deactivate under any trouble condition. Form C rated at 2.5 A @ 24
VDC Resistive.
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no
alarm or trouble conditions.
4.10.2 Programmable Relays
The control panel has two Form C programmable relays built into terminals labeled
RELAY 1 or RELAY 2. Each relay provides a normally open and a normally closed
contact.
To configure one or two programmable relays, follow these steps.
1. Wire Relay 1 and/or Relay 2 as needed for your application. See 4.10.1 for the
location of the relay terminals.
2. Default programming causes Relay 1 to activate for any supervisory. Relay 2 will
activate for any alarm. For relay applications that require different behavior see
Section 6.