beautypg.com

6 panel programming options, 1 system options, 1 synchronized strobes active when horns silenced – SilentKnight 5600 User Manual

Page 69: 2 silence/reset inhibit enabled, 3 water flow delay, 4 installer code (user id), 5 alarm verification time, 6 auto test, 7 low ac report delay, Panel programming options

background image

Programming

151450

6-7

6.6

Panel Programming Options

All customized programming options for the 5600 control panel are described in this
section and are available to be edited using the embedded web server of the control
panel.

6.6.1

System Options

6.6.1.1 Synchronized Strobes Active When Horns Silenced

The default configuration for this option is No. If set to Yes, strobes will remain on
when horns are silenced until a panel reset is issued.

6.6.1.2 Silence/Reset Inhibit Enabled

The default configuration for this option is NO. If set to Yes, Pressing either Reset or
Silence Buttons will be ignored for the duration of the delay (set to 30 seconds). The
inhibit feature delay is only active for the first alarm/supervisory signal.

6.6.1.3 Water Flow Delay

The water flow delay is a debounce time that is generally used to help reduce false
alarms during brief periods of water pressure fluctuation in a water riser. The default
setting is 1 second which is the minimum debounce time. You can set the water flow
delay within the range 1-90 seconds.

6.6.1.4 Installer Code (User ID)

This is the password used to lock the list of SLC devices found during the JumpStart
auto learn process. It is defaulted to 123456 and can be changed to any 4 to 8 digit
number.

6.6.1.5 Alarm Verification Time

Alarm verification is an optional false alarm prevention feature for smoke detectors
that verifies an alarm condition by resetting the smoke detector. The alarm verification
time can be set within the range of 1-250 seconds. For UL 864 installations this
option must be greater than 59 seconds. The default setting is 60 seconds.

6.6.1.6 Auto Test

Enter the hour/minutes (in 24 hour format) that you desire the control panel to send
the automatic test report.

6.6.1.7 Low AC Report Delay

This option determines the number of delay hours before a loss of AC is reported to