background image

System Operation

151450

7-3

7.10 Zone Disable Feature

To disable a zone, press the disable zone key that corresponds to the zone number
you wish to disable. When a zone is disabled all alarm events that occur while the
zone is disabled will be ignored. Zones that are disabled will be in trouble. The PZT
will sound the trouble cadence. The trouble LED for the specific zone along with the
general trouble LED will blink indicating that the zone is in trouble. If the silence key is
pressed after a zone is disabled, the trouble LEDs will be continuously on and the
PZT will silence.

To enable a zone which had been previously disabled, press the disable zone key
that corresponds to the zone number you wish to enable. Each pressing of the zone
disable key will toggle the disable/enable state for the zone.

Note: Followed by the Installers code in ULC installations. See Basic Operating Instructions.

7.11 Disabling Notification Circuits

There are 2 notification circuits on the 5600 control panel (NAC1 and NAC2). You can
disable them individually by pressing the NAC1 or NAC2 disable keys. A disabled
notification circuit will cause a trouble on the circuit. The PZT will sound the trouble
cadence. The trouble LED for the circuit along with the general trouble LED will blink
indicating trouble. If the silence key is pressed, the trouble LEDs will be continuously
on and the PZT will silence.

Pressing the NAC disable key when the circuit is already disabled will enable the
circuit. Each pressing of a NAC disable key will toggle the disable/enable state for the
circuit.

7.12 Loss of AC power

When AC is present and above the brown out threshold, the AC LED will be on
continuously. When AC power is off or below the brown out threshold, the AC LED
will blink. The GENERAL TROUBLE LED will blink also. The trouble relay will activate
for loss of AC once the reporting delay for reporting loss of AC power has been
reached. The default setting for this delay is 3 hours. If the silence key is pressed, the
trouble LEDs will be continuously on and the PZT will silence.

7.13 Remote Connection Feature

(ULC Installations Only)

To disconnect the communication paths to the Central Station and/or remote stations,
press the walk test button and the Acknowledge button at the same time. The PZT on
the panel will sound and the General Trouble LED will be flashing. This feature will
remain active until you press the Walk Test and Acknowledge buttons again.