7 dialer account programming options, 1 account number, 2 phone number – SilentKnight 5600 User Manual
Page 75: 3 reporting format, 4 reporting filters

Programming
151450
6-13
6.6.7
Dialer Account programming Options
Up to two accounts can be used for reporting events to the central station. A typical
reason to use multiple reporting accounts might be to have one account for reporting
alarms and a different account for reporting supervisories and troubles. The
programming options for each account are described below.
6.6.7.1 Account Number
Up to six digits allowed for SIA formats or up to four digits for contact ID format.
Default account numbers are blank.
6.6.7.2 Phone Number
Enter the phone number to call the central station. Default setting is blank.
The following special characters are available:
Table 6-4:: Special Dialing Characters
6.6.7.3 Reporting Format
Choose SIA8 (up to 8 events per call), SIA20 (up to 20 events per call) or contact ID
reporting format. Default setting is contact ID.
6.6.7.4 Reporting Filters
Selecting the Must option forces the event type to be reported to the account even if it
was already reported to another account. Selecting the Yes option will insure that the
event type gets to at least one account. Selecting the No option means that the event
type will not be reported to this account. The default setting is No.
Selecting No for all report filters in both accounts effectively disables the dialer.
#
Pound (or number) key on the telephone
*
Star key on the telephone
,
Comma (character for 2-second pause)