Model 5600 Installation and Operation Manual

5-2

151450

5.3

Wiring Requirements for SLC Devices

The following information applies to all SLC devices. Refer to the section that
describes the type of device you are installing for details.

5.3.1

Wiring SLC in Style 4 (Class B) Configuration

No special wire is required for addressable loops. The wire can be untwisted,
unshielded, solid or stranded as long as it meets the National Electric Code 760-121
requirements for power limited fire protective signaling cables. Wire distances are
computed using copper wire.

Maximum wiring resistance is 40 ohms to the farthest SLC device.

Maximum loop length depends on the wire gauge.

All SLC wiring is Supervised, and Power-limited.

Table 5-1: Maximum wiring distance for SLC devices

Wire Gauge

Max. Distance for SLC devices

22 AWG

1200 feet

18 AWG

3100 feet

16 AWG

4900 feet

14 AWG

7900 feet

12 AWG

10,000 feet