Programming

151450

6-9

6.6.2

Zone Programming

6.6.2.1 SLC Addresses Within Each Zone

Each zone has 15 alarm SLC addresses and 5 supervisory SLC addresses assigned
to it as described in table 6.1. For each SLC address within a zone, the SLC device
type choices are Unused, Detector, Manual Pull Switch, Latching Water Flow Switch
or Non-Latching Water Flow Switch. The default setting is that all points are unused.

6.6.2.2 Zone Silenceable

When an alarm occurs within a zone, there is a programming option that allows the
outputs to be silenceable or not. If you want the SILENCE key to be able to silence
outputs triggered by active alarms within the zone select YES for this option. The
default setting is Yes.

6.6.2.3 Zone Type

A zone can be either a one count zone or an alarm verification zone. The default
setting is one count. A one count zone has an immediate alarm when a single
detector goes into alarm.

Alarm verification is an optional false alarm prevention feature for smoke detectors
that verifies an alarm condition by resetting the smoke detector. If the alarm condition
still exists by the time the reset cycle has completed, the detector will go into alarm. If
the detector is no longer in alarm, the initial alarm is ignored. The alarm verification
sequence for a detector does not occur if the zone is already in alarm.

6.6.3

Output Point Programming

For each output SLC address you can select that a device is present or unused. The
default setting for all output points is unused.