Agency Listings, Approvals, and Requirements

151450

2-3

i)

Connection to party line service is subject to state tariffs. Contact the state public
utility commission, public service commission or corporation commission for
information.

j)

If your home has specially wired alarm equipment connected to the telephone
line, ensure the installation of this 5600 does not disable your alarm equipment. If
you have questions about what will disable alarm equipment, consult your
telephone company or qualified installer.

Electrical Safety Advisory:

Parties responsible for equipment requiring AC power should consider including an
advisory notice in their customer information suggesting the customer use a surge
arrestor. Telephone companies report that electrical surges, typically lightning
transients, are very destructive to customer terminal equipment connected to AC
power sources. This has been identified as a major nationwide problem.

2.2

Underwriters Laboratories (UL)

2.2.1

Requirements for All Installations

General requirements are described in this section. When installing an individual
device, refer to the specific section of the manual for additional requirements. The
following subsections list specific requirements for each type of installation (for
example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems,
and so on).

1. All field wiring must be installed in accordance with NFPA 70 National Electric

Code.

2. Use ONLY the addressable smoke detectors specified in Section 5.1 of this man-

ual.

3. Use UL listed notification appliances compatible with the 5600, choose from those

specified in the Appendix at the back of this manual.

4. A full system checkout must be performed any time the panel is programmed.

Restricted Options:

The loss of AC signal is defaulted to 3 hours however the system allows settings
from 0 - 30 hours. For UL certified installations this number must be set from 1 to
3 hours.

The system allows the Alarm Verification time to be set from 1 to 255 seconds.
For UL certified installations the setting must be a maximum of 60 seconds.

Call forwarding shall not be used.

Waterflow and Supervisory have to be set to Latching as shown in the restricted
options table in Section 6. See Table 6-1:.